  FORMULAE AND RELATED DETAILS
 
  CAPTURE OF CONTAMINATED AIR
 
 
Capture of contaminated air
Type of mouthOpeningDimens.Required flow
GROOVEH / L =0.2Q = 13.500 va Ld
GROOVE with flangeH / L =0.2Q = 10.000 va Ld
UNCOVERED RIMH / L =0.2Q = 3600 va
(10 d² + S)
RIM FLANGEH / L =0.2Q = 2750 va
(10 d²+ S)
S= L+ H
CABINIn line with the functionQ = 3.600 va
GROOVEIn line with the functionQ = 5.000 vaPD
P = Perimeter
 
 
 
 
 
 
 